Delta EH 15KVA 240V Online UPS 3 Phase In 1 Phase Out (No Battery)
Technical Specifications
Model
EH-15K
Power Rating
12 kW
Input
Nominal Voltage: 220/380 Vac, 230/400 Vac, 240/415 Vac
Voltage Range: 208~304 Vac (50~100% load)
305~477 Vac: (100% load)
Power Factor :> 0.95 (full load)
Frequency: 50/60 Hz
Output
Voltage: 220/230/240 Vac
Voltage Harmonic Distortion: < 3% (linear load)
Voltage Regulation: ± 2%
Frequency: 50/60 Hz ± 0.1 Hz
Overload Capacity:
≤ 105%: continuous
≤ 106~110%: 10 minutes
≤ 111~125%: 5 minutes
≤ 126~150%: 30 seconds
Battery
Battery Voltage: 240 Vdc
Charge Current: Built-in: 4 A
Additional charger board (optional): 4 A
Charge Voltage
Float charge 272 ± 2 Vdc
Boost charge 280 Vdc
Communication Interfaces
SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1,
REPO Port x 1, Charger Detection Port x 1
Conformance
Safety & EMC
CE, IEC62040-1, IEC62040-2
Other Features
Emergency Power Off
Local and remote
Maintenance Bypass Switch
Built-in
Efficiency
Online Mode: 91%
ECO Mode: 96%
Environment
Operating Temperature: 0~40ºC
Relative Humidity: 5~95% (non-condensing)
Audible Noise
< 60 dBA
Physical Dimensions (W x D x H)
250 x 610 x 650 mm
Weight
45 Kg
Delta EH 15KVA 240V Documents